Tripp Lite's HTR22-3U Pure Sine Wave
2200VA/1600W on-line, double-conversion UPS system prevents media data
loss, equipment freeze-ups, downtime and equipment damage due to power
outages, voltage fluctuations and transient surges. Provides full-time
sine wave 100, 110 or 120V +/-2% output with zero transfer time between
AC and battery operation. Actively converts raw incoming AC power to DC,
then re-converts output back to completely regulated, filtered AC
output. Operates continuously without using battery power during
brownouts to 65V and overvoltages to 138V. Network-grade AC surge and
EMI/RFI line noise suppression. Requires only 3 rack spaces (3U). Large
internal batteries provide 18 min. half-load runtime and 6 min. full
load runtime; runtime is expandable with optional BP72V15-2U and
BP72V28RT-3U external battery packs. 2200VA/1600W power handling
capacity is compatible with audio/video components and other sensitive
electronic applications. Includes 9 UPS-supported outlets arranged in
two switchable load banks that can be individually controlled via
software interface to reboot selected equipment on demand or
automatically shed less significant loads to extend battery runtime for
more critical equipment. Supports real time UPS communications via DB9
serial port or SNMPWEBCARD slot for the ultimate in IP remote access,
control and diagnostics capability with email notification. Supports
detailed monitoring of equipment load levels, self-test data and utility
power conditions via both network interfaces. Includes PowerAlert
monitoring software and complete cabling. Multi-function audible alarms
and front-panel LEDs provide at-a-glance notification of UPS and line
power status. Attractive all-black color scheme. $250,000 connected
equipment insurance (USA and Canada Only) |
Features |
- Provides perfectly regulated sine
wave output within 2% of 120V under all usage conditions
- 2200VA/1600W power handling
capacity compatible with control systems, HD sources, Audio/Video
editing suites, digital consoles, DVD/music/PCs/servers, RAIDs,
media centers, PVRs/DVRs, boardrooms, digital processors/EFX, racks
and other sensitive electronics
- Removes harmonic distortion, fast
electrical impulses, frequency variations and other hard-to-solve
power problems not addressed by other UPS types
- Corrects line voltage conditions
as low as 65V and as high as 138V back to 120V (+/-2%) values
- 2 switchable load banks (each with
4 outlets) enable remote outlet management for load shedding or
remote reboot of individual devices from anywhere in the world
- Standard internal battery set
offers 18 min. runtime at half load (800W) and 6 min. at full load
(1600W)
- Optional BP72V15-2U external
battery pack increases runtime to 98 min. at half load (800W) and 41
min. at full load (1600W); limit 1
- Optional BP72V28RT-3U external
battery pack increases runtime to 160 min. at half load (800W) and
69 min. at full load (1600W); multi-pack compatible
- Fault-tolerant auto-bypass
maintains continuous utility output to connected equipment, even in
cases where the UPS suffers internal failure and requires
maintenance
- Offers complete UPS monitoring
through included DB9 interface or SNMP interface (requires optional
SNMPWEBCARD), or the monitoring of any number of additional UPS
systems over IP with included PowerAlert monitoring software
- PowerAlert UPS monitoring and
unattended shutdown software enables configurable network broadcast
messaging, pager and email notification, event logging and running
user-defined script commands
- Front panel LEDs offer current
monitoring and battery charge level information
- UPS ships fully assembled in full
compliance with DOT regulations; no time-consuming connection of
internal batteries by user required
- $250,000 Ultimate Lifetime
Insurance (USA and Canada Only)
|
Specifications |
OUTPUT |
Output Volt Amp Capacity (VA) |
2200 |
Output Watt Capacity (watts) |
1600 |
Nominal Output Voltage(s) Supported |
120V |
Frequency compatibility |
50 / 60 Hz |
Frequency compatibility details |
Output frequency matches input nominal on
startup |
Output voltage regulation (line mode) |
+/- 2% |
Built-in UPS output receptacles |
4 5-15R outlet(s); 4 5-15/20R outlet(s); 1
L5-20R outlet(s) |
Built-in controllable switched load banks |
Two switchable four-outlet load banks
(bank 1 - four 5-15R outlets, bank 2 - four 5-15/20R outlets) |
Output circuit breaker |
15A branch rated breakers (x2) protect 4
outlets each, L5-20R outlet is unbreakered |
INPUT |
Rated input current (at maximum load)
|
16A |
Nominal Input Voltage(s) Supported |
120V AC |
UPS input connection type |
5-20P |
UPS Input cord length (ft.) |
10 ft. |
UPS Input cord length (m) |
3.05 |
Recommended Electrical Service |
120V 20A dedicated circuit |
Voltage compatibility (VAC) |
120 |
BATTERY |
Full load runtime (minutes) |
7 min. (1600w) |
Half load runtime (minutes) |
18 min. (800w) |
Expandable battery runtime |
Supports extended runtime with optional
external battery packs BP72V15-2U (limit 1) and BP72V28RT-3U (multi-pack
compatible) |
External battery pack compatibility |
BP72V15-2U (limit 1); BP72V28RT-3U
(multi-pack compatible) |
DC system voltage (VDC) |
72 |
Battery recharge rate (included batteries)
|
Less than 6 hours from 10% to 80% |
Replacement battery cartridge (internal
UPS battery replacement) |
RBC96-3U (quantity 1) |
Battery Access |
Hot-swap battery replacement supported via
front access panel |
Typical battery lifespan |
3-6 years, depending on usage |
VOLTAGE REGULATION |
Voltage regulation description |
On-line, double-conversion power
conditioning maintains output within 2% of 100/110/120 volts at all
times |
Overvoltage correction |
Maintains output of selected nominal +/-2%
during overvoltages to 138V AC |
Undervoltage correction |
2% output voltage regulation during
undervoltages to 80 |
Severe undervoltage correction |
Maintains output within 2% of nominal
during undervoltages to 65 (under 70% load only) |
LEDS ALARMS & SWITCHES |
LED Indicators |
14 LEDs indicate line power, online mode,
economy/bypass mode, on-battery, overload, battery low, replace battery
and fault status information; 4-LED meter displays load and battery
charge levels; LED panel rotates for viewing in rack/tower formats |
Alarms |
Multi-function audible alarm with
distinctive ring patterns offer notification of backup operation (2 sec.
on / 0.5 sec. off), low battery warning (1.25 sec. on / 0.5 sec. off),
overload (sounds continuously), UPS fault (4.2 sec. on / 1 sec. off),
input voltage out of frequency (2.1 sec. on / 0.14 sec. off) and high
input voltage (2.1 sec. on 0.07 sec. off) |
Switches |
Power off/on switch and battery
charge/load level display select switch |
SURGE / NOISE SUPPRESSION |
UPS AC suppression joule rating |
1014 joules |
EMI / RFI AC noise suppression |
Yes |
AC suppression response time |
Instantaneous |
PHYSICAL |
Installation form factors supported with
optional accessories |
2 post rackmount (2POSTRMKITWM); Tower
(2-9USTAND) |
UPS / Power Module dimensions in primary
form factor (height x width x depth / inches) |
5.2 x 17.5 x 20.5 |
UPS / Power Module weight (lbs) |
74.9 |
UPS housing material |
Steel |
Cooling method |
Built-in cooling fan |
ENVIRONMENTAL |
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40
degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50
degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC mode BTU / hr. (full load) |
812.9 |
Battery mode BTU / hr. (full load) |
885.6 |
COMMUNICATIONS |
Communications interface |
DB9 Serial; Contact closure; EPO
(emergency power off); Slot for SNMP/Web interface |
WatchDog compatibility |
Compatible with Tripp Lite's Watchdog
system service to restore operation to locked equipment through soft
reboot of application / OS or hard power off/on reboot of connected
equipment - ideal for unattended kiosk applications |
EPO port |
Supports Emergency Power Off function via
set of dedicated built-in EPO jacks |
SNMP compatibility |
Slot for optional SNMPWEBCARD accessory
(Tripp Lite Model # SNMPWEBCARD) |
Software and cabling included |
PowerAlert Software CD-ROM and complete
cabling |
LINE / BATTERY TRANSFER |
Transfer time |
No transfer time (0 ms.) in online,
double-conversion mode |
Low voltage transfer to battery power
(setpoint) |
80V (100% load), 65V ( <70% load) |
High voltage transfer to battery power
(setpoint) |
138 |
SPECIAL FEATURES |
Cold Start (startup in battery mode during
a power failure) |
Cold-start operation supported |
Appearance |
Attractive all-black color scheme |
CERTIFICATIONS |
Certifications |
Tested to UL1778 (USA), cUL (Canada), NOM
(Mexico), FCC Class A (emissions) |